1/03 UDC 6300 Process Controller Product Manual 81
4.5 Accutune Set Up Group, Continued
Table 4-4 Accutune Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
CRITERIA2*
NORMAL
FAST
TUNING CRITERIA FOR LOOP 2 (SETPOINT
ADAPT) - Select a criteria best suited for your
process on Loop 2
NORMAL - Original critical damping (no overshoot)
FAST - a more aggressive tuning with a minimal
possible overshoot of less than 0.5%.
For Example: Slightly underdamped
AT ERROR
See Section 5 -
Operation for a list of
error prompts.
ADAPTIVE TUNE ERROR STATUS LOOP1
When an error is detected in the Accutune process,
an error prompt will appear.
AT ERROR2
See Section 5 -
Operation for a list of
error prompts.
ADAPTIVE TUNE ERROR STATUS LOOP 2
When an error is detected in the Accutune process,
an error prompt will appear.
* Applies to “SP Only” and “SP+PV” tuning only