1/03 UDC 6300 Process Controller Product Manual 125
4.13 Options Set Up Group, Continued
Table 4-12 Option Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
DIG IN 3
DIGITAL INPUT THREE SELECTIONS — Digital
Input 3 is internally connected (shares rear
terminals) with the Alarm1 and Digital Output 1.
The controller returns to its original state when
contact opens, except where noted.
If the selection for the Digital Inputs are in conflict
with each other, whichever switch is closed first will
take precedence. If multiple switches are closed
simultaneously, then the lowest numbered Digital
Input takes precedence.
Digital Inputs and Logic Gate outputs configured to
turn on a Digital Output have the same priority.
These operate as an OR function with one another.
The Digital Output will be active if either the Digital
Input or the Gate Output is in a TRUE condition.
If the controller is in Communications Slave mode on
either loop, then the switches are disabled.
Contact closure enables one of the following:
NONE
NO DIGITAL INPUT SELECTIONS
TO MANUAL
TO MANUAL — Contact closure puts the controller
into manual mode.
TO SP1
TO LOCAL SETPOINT — Contact closure puts the
controller into local setpoint 1.
TO SP2
TO LOCAL SETPOINT TWO — Contact closure
puts the controller into local setpoint 2.
TO SP3
TO LOCAL SETPOINT THREE — Contact closure
puts the controller into local setpoint 3.
TO RUN
TO RUN— Contact closure starts a Setpoint ramp.
TO HOLD
TO HOLD — Contact closure suspends Setpoint
Ramp. Contact open runs ramp.
TO PID2
TO PID2 — Contact closure selects PID Set 2.
PV IS IN1
PV = INPUT 1-Contact Closure selects PV = Input 1.
PV IS IN2
PV = INPUT 2-Contact Closure selects PV = Input 2.
PV IS IN3
PV = INPUT 3-Contact Closure selects PV = Input 3.
PV IS IN4
PV = INPUT 4-Contact Closure selects PV = Input 4.
PV IS IN5
PV = INPUT 5-Contact Closure selects PV = Input 5.
RSP - IN1
REMOTE SETPOINT FROM INPUT 1— Contact
closure selects Input 1 as the Remote Setpoint.
Table 4-12 continued on next page