80 UDC 6300 Process Controller Product Manual 1/03
4.5 Accutune Set Up Group, Continued
Table 4-4 Accutune Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
ACCUTUNE 2
DISABL
TUNE
SPoNLY
TUNE + PV
SP Only + PV
ACCUTUNE - Loop 2 Available only if configured
for 2Loop or Cascade.
DISABLE ACCUTUNE 2 – Disables the Accutune
function for Loop 2.
TUNE - same as ACCUTUNE
SETPOINT ONLY Same as ACCUTUNE
TUNE + PROCESS VARIABLE- Same as
ACCUTUNE
SETPOINT ONLY PLUS PROCESS VARIABLE -
Same as ACCUTUNE
SP CHANG*
5 to 15%
SETPOINT CHANGE - The minimum setpoint
change that will result in re-tuning must be
configured between 5% and 15%:( i.e. If the range is
0 to 2400 and 5% is configured, re-tuning will occur if
the setpoint change is 120 or larger.)
PROC GAIN*
0.10 to 10.00
PROCESS GAIN This is the Gain of the process
being tuned on Loop 1. It is automatically calculated
during tuning process. This is normally a READ only
value. It should only need to be changed if the cont-
roller fails to identify the process. In this case, set the
value to the algebraic value of PV in percent, divided
by output in percent while in the manual mode.
SP CHANG2*
5 to 15%
SETPOINT CHANGE LOOP 2- The minimum
setpoint change on Loop 2 that will result in re-tuning
must be configured between 5% and 15%:
PROC GAIN 2*
0.10 to 10.00
PROCESS GAIN LOOP 2 This is the Gain of the
process being tuned on Loop 2. It is automatically
calculated during tuning process. This is normally a
READ only value. It should only need to be changed
if the controller fails to identify the process. In this
case, set the value to the algebraic value of PV in
percent, divided by output in percent while in the
manual mode.
ATTENTION
Note you must disable Accutune to
change tuning constant values from the keyboard.
CRITERIA*
NORMAL
FAST
TUNING CRITERIA (SETPOINT ADAPT) - Select a
criteria best suited for your process on loop 1.
NORMAL - Original critical damping (no overshoot)
FAST - a more aggressive tuning with a minimal
possible overshoot of less than 0.5%.
* Applies to “SP Only” and “SP+PV” tuning only
Continued on next page