116 UDC 6300 Process Controller Product Manual 1/03
4.12 Control2 Parameters Set Up Group
Introduction
The functions listed in this group deal with how Loop 2 of a Two Loop
Process controller will control the process including: PV Source, Number
of tuning parameter sets, Setpoint source, Tracking, Power-up recall,
Setpoint limits, Output direction, rate and limits, Dropoff, Deadband and
Hysteresis.
Control2 group
prompts
Table 4-11 lists all the function prompts in the Control2 setup group and
their definitions.
Table 4-11 Control2 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PV2 SRC
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN ALG 1
IN ALG 2
PROCESS VARIABLE 2 SOURCE - select the
source of the Process Variable for Loop 2.
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT ALGORITHM 1
INPUT ALGORITHM 2
PID SETS
NUMBER OF TUNING PARAMETER SETS — This
selection lets you choose one or two sets of tuning
constants (gain, rate, and reset).
1 ONLY
ONE SET ONLY — Only one set of tuning
parameters is available. Configure the values for:
Gain (proportional band)
Rate
Reset Time
Cycle Time (if time proportional is used)
2KEYBD
TWO SETS KEYBOARD SELECTABLE — Two
sets of tuning parameters can be configured and can
be selected at the operator interface or by using the
Digital Inputs.
Press LOWR DISP
key until you see "PID SET3"
or “PID SET4” to switch between sets. Configure the
values for:
Gain#3, Rate#3 , Reset#3, Cycle3Time
Gain #4, Rate #4, Reset#4, Cycle#4 Time
See Subsection 5.10 for procedure.
2PV SW
TWO SETS PV AUTOMATIC SWITCHOVER
When the process variable is GREATER than the
value set at prompt "SW VALUE" (Switchover
Value), the controller will use Gain3, Rate3, Reset3,
and Cycle 3Time. The active PID SET can be read in
the lower display.
When the process variable is LESS than the value
set at prompt "SW VALUE," the controller will use
Gain #4, Rate #4, Reset #4, and Cycle #4 Time. The
active PID SET can be read in the lower display.
Other prompts affected: SW VALUE
Table 4-11 continued on next page