1/03 UDC 6300 Process Controller Product Manual 89
4.6 Algorithm Data Set Up Group, Continued
Table 4-5 Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN ALG 1
(continued)
INPUT ALGORITHM 1 (continued)
FFWD MULT
FEEDFORWARD MULTIPLIER - applies to Loop 1
only and uses Input A, following a Ratio and Bias
calculation as a value multiplied by the PID
computed output value and sent, as an output value,
to the final control element. This algorithm will only
function in automatic mode.
Controller Output = PID Output x (Input A x Ratio + Bias )
AA
CONSTNT K
0.001 to 1000
WEIGHTED AVERAGE RATIO OR K CONSTANT
FOR MATH SELECTIONS - Only applicable for
algorithms "WTD AVG" or Math selections
"√ MUL DIV ", √ MULTIPLY ", "MULT DIV", or
"MULTIPLY"
CALC HIGH
–999 to 9999
CALCULATED VARIABLE HIGH SCALING
FACTOR FOR INPUT ALGORITHM 1 - Does not
apply to Feedforward Algorithms.
CALC LOW
–999 to 9999
CALCULATED VARIABLE LOW SCALING
FACTOR FOR INPUT ALGORITHM 1 - Does not
apply to Feedforward Algorithms.
ALG 1 IN A
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
OUTPUT 1
OUTPUT 2
ALGORITHM 1, INPUT A SELECTION - will
represent one of the available selections
OTHER ALG - Algorithm 1 is performed before
Algorithm 2. If ALG2 is used in ALG1, there is a
one cycle delay
ALG 1 IN B
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
OUTPUT 1
OUTPUT 2
ALGORITHM 1, INPUT B SELECTION - will
represent one of the available selections
OTHER ALG - Algorithm 1 is performed before
Algorithm 2. If ALG2 is used in ALG1, there is a
one cycle delay
ALG 1 IN C
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
ALGORITHM 1, INPUT C SELECTION - will
represent one of the available selections
Table 4-5 continued on next page