1/03 UDC 6300 Process Controller Product Manual 163
5.7 Setpoints, Continued
Switching between
local and remote
setpoints
You can switch between Local and Remote setpoints. Use the procedure
in Table 5-15 to switch between setpoints.
Table 5-15 Procedure for Switching Between Local and Remote
Setpoints
Step Operation Press Action
1
Select Local
setpoint
RSP
CAS
Until you see:
Lower Display
Upper Displa
y
The PV value
SP, SP2, or SP3 and
the local setpoint value
2
Change the
Local setpoint
value
or
The REMOTE setpoint cannot be
changed at the keyboard.
3
Select Remote
setpoint
RSP
CAS
again
You will see:
Lower Display
Upper Display
The PV value
RSP and the remote
setpoint value
Continued on next page