1/03 UDC 6300 Process Controller Product Manual 65
3.20 Display Parameters Set Up Group
Introduction
This data deals with the Decimal Place, Units of Temperature, Power
Frequency, and Process ID Tag.
Function prompts
Table 3-17 lists all the function prompts in the “Display” Set Up group.
Table 3-17 Display Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
DECIMAL
Control Loop 1 Decimal
Place
XXXX
XXX.X
XX.XX
X.XXX
ATTENTION
Auto-ranging will
occur to whichever decimal place
has been selected.
XXXX
DECIMAL2
Control Loop 2 Decimal
Place
XXXX
XXX.X
XX.XX
X.XXX
XXXX
TEMP UNIT
Control Loop 1
Temperature Units
DEG F
DEG C
NONE
NONE
PWR FREQ
Power Frequency 60 Hertz
50 Hertz
60HZ
2 LOOP DIS
Bargraph Display SPnPVnOn
L1 L2 On
L1 –– On
–– L2 On
SPnPVnON
SP GRAPH
Setpoint Indication FULL
ONE BAR
FULL
ID TAG
Identification Tag DISABLE
ENABLE
ENABLE
PV TAG
Process Variable Tag DISABLE
ENABLE
DISABLE
PV TAG2
Process Variable Tag DISABLE
ENABLE
DISABLE
TAG
ID or PV tag
ConfigurationTag
Letters: A to Z
Numbers: 0 to 9
Others: >, <, #, /, \, . ,
(blank), –, ., °, =, ?,_,
^, V, +, *
- -
RATIO4SET
Ratio for Input 4 - Set from
the front of the controller
DISABLE
LOWR DISP
DISABLE
LANGUAGE
Display Language ENGLISH
FRENCH
GERMAN
ENGLISH