1/03 UDC 6300 Process Controller Product Manual 41
3.9 Accutune Set Up Group, Continued
Function prompts
Table 3-6 lists the function prompts in the “ACCUTUNE” Set Up group.
Table 3-6 Accutune Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
FUZZY
Fuzzy Overshoot
Suppression
DISABLE
ENABLE
Disabl
ACCUTUNE
Accutune DISABLE
TUNE (Demand Tuning)
SP ONLY (SP Tuning)
TUNE + PV
SP ONLY+ PV
Disabl
ACCUTUNE2
Accutune2 DISABLE
TUNE (Demand Tuning)
SP ONLY (SP Tuning)
TUNE + PV
SP ONLY + PV
Disabl
SP CHANG*
Setpoint Change Value 5 to 15% Input Span 10
PROC GAIN*
Process Gain 0.10 to 10.00 1.0
SP CHANG2*
Setpoint Change Value 5 to 15% Input Span 10
PROCGAIN2*
Process Gain 0.10 to 10.00 1.0
CRITERIA*
Tuning Criteria - Loop 1 NORMAL
FAST
FAST
CRITERIA2*
Tuning Criteria - Loop 2 NORMAL
FAST
FAST
AT ERROR
or
AT ERROR 2
(depending on Loop)
AccutuneError codes Read Only
NONE
OUT LIMIT
ID FAIL
ABORT
LOW PV
RUNNING
- -
* APPLIES TO “SP ONLY” AND “SP + PV) ONLY